Article number: 28 612 06 99

Anti-vacuum device

Flow form, version C
For installing on appliance connection fittings with backflow preventer, without anti-vacuum device.
Find contact person on site

Delivery data

  • Weight: 0,12 kg/Piece
  • Packing unit: 1

Technical data

  • Material: Brass, conform to German drinking water regulations
  • Certificates: DIN-DVGW
Hint
  • Together with appliance connection fittings with backflow preventer HP safety combination (EN 1717).
Mounting instructions
  • Downstream pipework must be flexible and removable.
  • The tube diffuser must be installed vertically and be fully accessible.
  • Tube diffusers must not be installed in rooms at risk of flooding.
  • The tube diffuser must be installed in a ventilated environment (clean atmosphere) and protected against frost/high temperatures.
  • No shut-off device may be installed downstream of the tube diffuser.
  • The minimum distance to the subsequent liquid level must be > 250 mm.
  • Tube diffusers must not be exposed to constant back pressure.